RBM Automatic Filling Unit for commercial HVAC applications.
During the normal operation of a heating system, part of the fluid is lost through the deaerators, in the form of steam mixed with gases that develop continuously in the circuit. The space left free by the fluid, if it is not properly reinstated, will be occupied by the gases which, dissolved, would form acid solutions that can lead to corrosion.
They are particularly suited to be used in heating systems with the precise task of re-integrating the water that comes out from the system. Kit consists of:
1) RBM SmartFiller M - automatic feeding unit that features calibration knob (50-400kPa), 500micron filter, isolation valve, check valve and pressure gauge.
2) RBM Airterm - threaded inline deaerator valve for eliminating microbubbles from systems via active part of 3-layer stainless steel cartridge mesh and via passive part of automatic float operated air vent.
3) Isolation Valve
4) 4-Way G1/2" Brass tee for connection to system and/or pressure vessel
5) RBM Safety Relief Valve
Compatible Fluid: Water Nominal Pressure: PN16
Maximum Operating Temperature: 80C
Safety Valve Calibration: 4 Bar (other sizes available upon request)
Connection Sizes: G1/2" M or G1/2" F